Numeros
Categories Financial Calculators Health Calculators Math Calculators Date & Time Construction Engineering Physics Business Education Lifestyle Converters Generators
About

Voltage Drop Calculator

Enter your wire gauge, one-way circuit length, and current to find the voltage drop across the run - useful for checking whether a wire run meets standard 3% guidance for branch circuits.

Voltage Drop Calculator

Live
Voltage drop
2.96 V
Percent drop
2.47%
Within 3% guidance?
Yes
Assumes a single-phase circuit at 75°C conductor temperature.

The formula

Voltage drop = (2 x K x I x L) / CM K = 12.9 for copper, 21.2 for aluminum (ohm-cmil/ft at 75°C) I = current in amps, L = one-way length in feet, CM = wire's circular mil area
Example

12 AWG copper wire (6,530 circular mils), 50 ft one-way, 15A load, 120V circuit: drop = (2 x 12.9 x 15 x 50) / 6530 ≈ 2.96V, or 2.47% - within the commonly recommended 3% guidance for branch circuits.

Step-by-step guide

  1. Select your wire gauge and confirm the conductor material.
  2. Enter the one-way length of the run - not the round-trip distance, since the formula already accounts for both directions.
  3. Enter the current the circuit will carry, and the source voltage.
  4. Check the percent drop against your application's guidance - 3% is a commonly cited target for branch circuits, and 5% for the combined feeder and branch circuit.

Why voltage drop matters

Excessive voltage drop means equipment at the end of a long circuit run receives less voltage than intended, which can cause dimmer lights, motors that run hotter and less efficiently, or electronics that behave unpredictably. It's a bigger concern on longer runs and higher-current circuits, which is why detached garages, workshops, or long outdoor runs often need a larger wire gauge than the same load would require over a short distance.

Note: This calculator estimates voltage drop for planning purposes. Actual electrical installations must meet your local electrical code and should be sized, installed, and inspected by a qualified electrician.

Common mistakes

Entering the round-trip wire length instead of the one-way length - the formula's factor of 2 already accounts for the return path.
Using the circuit breaker's rating instead of the actual expected load current - voltage drop should be calculated for the real anticipated current draw, not the maximum breaker size.

Frequently asked questions

What voltage drop percentage is acceptable?

3% is a commonly cited recommendation for a branch circuit alone, and 5% for the combined feeder plus branch circuit, though this is guidance rather than a strict universal code requirement in every jurisdiction - check your local electrical code.

Why does aluminum wire need a bigger gauge than copper for the same job?

Aluminum has higher resistance than copper for the same cross-sectional area, so an aluminum wire needs to be larger (more circular mils) to carry the same current with an equivalent voltage drop.

Does temperature affect voltage drop?

Yes - resistance increases with temperature, so a wire running hot will have somewhat more voltage drop than the same wire at a cooler temperature. This calculator uses the standard 75°C reference figure used in most NEC-based calculations.

Related calculators

See the full list of Engineering calculators, or try: