Enter your wire gauge, one-way circuit length, and current to find the voltage drop across the run - useful for checking whether a wire run meets standard 3% guidance for branch circuits.
Voltage Drop Calculator
LiveThe formula
12 AWG copper wire (6,530 circular mils), 50 ft one-way, 15A load, 120V circuit: drop = (2 x 12.9 x 15 x 50) / 6530 ≈ 2.96V, or 2.47% - within the commonly recommended 3% guidance for branch circuits.
Step-by-step guide
- Select your wire gauge and confirm the conductor material.
- Enter the one-way length of the run - not the round-trip distance, since the formula already accounts for both directions.
- Enter the current the circuit will carry, and the source voltage.
- Check the percent drop against your application's guidance - 3% is a commonly cited target for branch circuits, and 5% for the combined feeder and branch circuit.
Why voltage drop matters
Excessive voltage drop means equipment at the end of a long circuit run receives less voltage than intended, which can cause dimmer lights, motors that run hotter and less efficiently, or electronics that behave unpredictably. It's a bigger concern on longer runs and higher-current circuits, which is why detached garages, workshops, or long outdoor runs often need a larger wire gauge than the same load would require over a short distance.
Note: This calculator estimates voltage drop for planning purposes. Actual electrical installations must meet your local electrical code and should be sized, installed, and inspected by a qualified electrician.
Common mistakes
Frequently asked questions
What voltage drop percentage is acceptable?
3% is a commonly cited recommendation for a branch circuit alone, and 5% for the combined feeder plus branch circuit, though this is guidance rather than a strict universal code requirement in every jurisdiction - check your local electrical code.
Why does aluminum wire need a bigger gauge than copper for the same job?
Aluminum has higher resistance than copper for the same cross-sectional area, so an aluminum wire needs to be larger (more circular mils) to carry the same current with an equivalent voltage drop.
Does temperature affect voltage drop?
Yes - resistance increases with temperature, so a wire running hot will have somewhat more voltage drop than the same wire at a cooler temperature. This calculator uses the standard 75°C reference figure used in most NEC-based calculations.
Related calculators
See the full list of Engineering calculators, or try: